+966-533428898

    Flameproof Lighting

    Sourced and supplied across Saudi Arabia

    Hazardous area lighting has to satisfy two people who rarely talk to each other: the electrical engineer who needs the certification to match the zone, and whoever has to see well enough to work. So the enquiry needs the lux level and the mounting height alongside the zone, gas group and temperature class, because a luminaire certified for the area but mounted twelve metres up on a pipe rack may still leave a walkway too dark to inspect. LED has largely displaced fluorescent and discharge here, and the reason is maintenance access rather than efficiency — replacing a lamp in a Zone 1 luminaire means a permit, scaffold or a MEWP, and a fitting that lasts many years is worth a premium that has nothing to do with the electricity bill. One caution specific to this climate: LED life is a function of junction temperature, so a fitting rated for a temperate ambient will not deliver its published life on an unshaded rack here. State the ambient.

    What to state in your enquiry

    The more of this you send, the closer the first quotation lands.

    ZoneZone 1 or 2 for gas; Zone 21 or 22 for dust
    Gas group and temperature classIIA, IIB or IIC, and T1 to T6
    Ambient temperature rangeThe certificate and the LED life both depend on it
    Illuminance requiredLux on the working plane, and the area covered
    Mounting height and methodCeiling, wall, pole or pipe bracket, and the height
    Luminaire typeLinear, floodlight, wellglass, bulkhead or emergency
    Emergency functionState if integral battery backup and duration are required
    Supply voltage230 V at 60 Hz, or another supply available at the position
    Cable entriesNumber, size and thread, with certified glands
    Corrosion exposureCoastal or offshore — decides body material and finish
    IP ratingSeparate from the Ex protection concept
    ControlSwitched, photocell, or dimmed and controlled remotely
    DocumentationCertificate, photometric data and the marking plate details

    Standards we supply against

    • IEC 60079-0
    • IEC 60079-1
    • IEC 60079-7
    • IEC 60079-18
    • IEC 60598-1

    Which type do you need?

    Select one and it travels with your enquiry. Not sure? Leave it and describe the application instead.

    We source to specification. Send your requirement and we will come back with options, lead time and pricing.

    Also in Explosion-Proof Components