    A bank is the installed system rather than the cells in it, and what is being bought is a string design, a structure to hold it and a room that can safely contain it. Three things have to be settled together. The DC bus voltage and the cell chemistry fix the number of blocks in series; the autonomy and the discharge current fix how many strings sit in parallel, and parallel strings need equal-length interconnections or the current will not share. The rack or cabinet then has to carry a mass most people underestimate — a modest standby bank runs to several hundred kilograms — and be arranged so a technician can reach every terminal to torque and test it. And the room is part of the scope: charging evolves hydrogen, so ventilation is calculated rather than assumed, and IEC 62485-2 is the document that sets out how. Send the DC voltage, the load profile and the room dimensions.

    What to state in your enquiry

    The more of this you send, the closer the first quotation lands.

    DC bus voltageNominal system voltage — it fixes the blocks in series
    Load profileDischarge current and duration, including any step changes
    AutonomyRequired backup time at the stated load
    String configurationBlocks in series, and how many parallel strings
    InterconnectionEqual-length links between parallel strings for current sharing
    Rack or cabinetTiered rack, step rack or enclosed cabinet, and the floor loading
    Maintenance accessEvery terminal must be reachable to torque and test
    Room ventilationCalculated for hydrogen evolution per IEC 62485-2
    Room temperatureCooling arrangement — heat is what shortens the bank's life
    ChargerExisting charger, its float and boost voltages and current limit
    MonitoringBlock voltage, temperature and impedance monitoring if required
    Protection and isolationDC fuses, isolator and the earthing arrangement
    CommissioningState if a capacity discharge test is required at handover

    Standards we supply against

    • IEC 62485-2
    • IEC 60896-21
    • IEC 60896-22

    Which type do you need?

    Select one and it travels with your enquiry. Not sure? Leave it and describe the application instead.

    We source to specification. Send your requirement and we will come back with options, lead time and pricing.