+966-533428898

    MV Power Cables

    Sourced and supplied across Saudi Arabia

    At medium voltage the cable is the cheap part of the job. The cost and the risk sit in the terminations, the joints and the metallic screen, and an enquiry that lists only a size and a length leaves all three unpriced. Three things need to be stated. The insulation level first: a system with fast earth-fault clearance is normally served by 100 percent insulation level, while a system that may run with a sustained earth fault needs 133 percent, and that is a system property rather than a preference. The screen bonding second — both ends, single-point with a parallel earth continuity conductor, or cross-bonded — because it decides circulating current, the effective rating and what accessories are needed. And the accessory schedule third: indoor and outdoor terminations, straight joints, and whether the site expects heat-shrink or cold-shrink workmanship. Send the single line diagram, the earthing philosophy and the route with its drum-length constraints.

    What to state in your enquiry

    The more of this you send, the closer the first quotation lands.

    Rated voltageSuch as 6/10 kV, 12/20 kV or 18/30 kV
    Insulation level100 percent or 133 percent — set by the earth fault clearance time
    Conductor material and sizeCopper or aluminium, cross-section per phase
    Screen sizeMetallic screen cross-section for the earth fault current and duration
    Screen bondingBoth ends, single point, or cross-bonded
    ConfigurationThree single cores in trefoil or flat, or one three-core cable
    Installation methodDirect buried, in duct, on tray, or in a trench
    Ground temperature and resistivityDesign maxima for the buried section
    TerminationsIndoor and outdoor counts, heat-shrink or cold-shrink
    JointsStraight joints required, and any transition joint to existing cable
    Drum lengthsContinuous lengths, and the pulling constraints on the route
    TestingPartial discharge, VLF or other commissioning tests required
    CertificationType and routine test certificates, and any approved vendor list

    Standards we supply against

    • IEC 60502-2
    • IEC 60228
    • IEC 60332-1-2

    Which type do you need?

    Select one and it travels with your enquiry. Not sure? Leave it and describe the application instead.

    We source to specification. Send your requirement and we will come back with options, lead time and pricing.