    Emergency Showers

    Sourced and supplied across Saudi Arabia

    The hard part of an emergency shower in the Eastern Province is not the shower, it is the water temperature. ANSI/ISEA Z358.1 asks for 75.7 litres per minute for a full fifteen minutes at a tepid 16 to 38 degrees Celsius, and a supply line running exposed across a yard in July does not deliver tepid water — it delivers water hot enough that a casualty steps out of the stream, which is the specific failure the fifteen-minute figure exists to prevent. Solving it means a tempering valve, a shaded or insulated run, a recirculating loop, or a tank unit with active cooling, and that decision belongs in the enquiry rather than in commissioning. One more point worth settling early: the European series splits by setting, and EN 15154-1 is written for laboratories while parts 5 and 6 cover overhead and multiple-nozzle showers for other sites, so quoting part 1 for a process plant specifies the wrong document.

    What to state in your enquiry

    The more of this you send, the closer the first quotation lands.

    Standard namedANSI/ISEA Z358.1, or the applicable part of EN 15154
    Water supplyPlumbed mains, gravity tank, or self-contained tank unit
    Tepid water methodTempering valve, insulated line, recirculation, or active cooling
    Supply temperatureState the actual line temperature at the worst hour of the day
    Available flow and pressureThe line must sustain 75.7 L/min for 15 minutes
    Combination unitShower only, or shower with eye or eye/face wash
    MountingFloor-standing pedestal, wall, ceiling, or mobile skid
    MaterialsGalvanised, stainless or coated — state the corrosion exposure
    Hazardous areaState any Ex requirement for heat tracing or alarms
    Alarm and monitoringFlow switch, beacon, sounder or BMS signal
    Waste waterDrain, sump or containment — state where the water goes
    Testing accessWeekly activation is expected; state how it will be run off
    Quantity and locationsUnits, and the travel time from each hazard point

    Standards we supply against

    • ANSI/ISEA Z358.1
    • EN 15154-1
    • EN 15154-5
    • EN 15154-6