    Distribution Transformers

    Sourced and supplied across Saudi Arabia

    The specification error that costs money here is ambient temperature. IEC 60076 ratings are referenced to ambient conditions well below what a transformer standing in an unshaded compound in the Eastern Province actually sees, and a unit ordered at its nameplate kVA on the assumption of a temperate site is derated in practice from the day it is energised β€” losing capacity precisely in the summer months when the connected air conditioning load peaks. Either the site ambient goes into the enquiry so the rating is chosen against it, or the transformer is specified with a higher temperature class or forced cooling. Two other things belong in the first message: the vector group and impedance, because these must agree with the existing system if the unit will ever run in parallel or feed a protection scheme already set, and whether the installation is indoors, which usually decides cast resin over oil-filled on fire grounds.

    What to state in your enquiry

    The more of this you send, the closer the first quotation lands.

    Rated powerkVA, and whether that is the ONAN or forced-cooled figure
    Voltage ratioPrimary and secondary, at 60 Hz for the Saudi system
    Site ambient temperatureState the design maximum β€” it changes the usable rating
    Cooling typeONAN, ONAF, or air natural for cast resin
    Insulation typeOil-filled, or cast resin where the unit is indoors
    Vector groupDyn11 or as required to match the existing system
    ImpedancePercentage β€” must suit parallel operation and fault levels
    Tap changerOff-circuit or on-load, and the tap range required
    Enclosure and mountingIndoor, outdoor, pad-mounted, pole-mounted or kiosk
    Corrosion protectionCoastal chloride exposure at Dammam, Jubail or Ras Tanura
    LossesState if guaranteed no-load and load losses are evaluated in the bid
    Utility approvalState if a utility or Aramco approved vendor list applies
    Testing and documentationRoutine, type and special tests, and the certificates required

    Standards we supply against

    • IEC 60076-1
    • IEC 60076-2
    • IEC 60076-3
    • IEC 60076-11

    Which type do you need?

    Select one and it travels with your enquiry. Not sure? Leave it and describe the application instead.

    We source to specification. Send your requirement and we will come back with options, lead time and pricing.