    Isolation Transformers

    Sourced and supplied across Saudi Arabia

    An isolation transformer is bought for what it separates, not for what it converts, and that is why a kVA figure alone is never enough to quote against. The ratio is usually one to one. What the buyer is actually specifying is a galvanic break: a supply whose secondary has no reference to the site earth until you give it one, so that a single earth fault on a sensitive circuit does not trip the source or put fault current through an instrument reference. State the reason and the right unit follows. Separating a noisy drive from an analyser needs an electrostatic screen between windings and a stated coupling capacitance; creating an unearthed IT system for a control room or a test bay needs a double-wound unit with insulation monitoring; separating a portable tool circuit is a different, simpler product again. Tell us what problem the separation is solving and where the secondary earth reference will be made.

    What to state in your enquiry

    The more of this you send, the closer the first quotation lands.

    Purpose of isolationNoise rejection, unearthed IT system, or safety separation
    Voltage ratioUsually 1:1 — state if the secondary voltage also changes
    Rated powerkVA, allowing for the inrush of the connected equipment
    Winding constructionDouble-wound — an auto-transformer gives no galvanic separation
    Electrostatic screenSingle or double screen, and any coupling capacitance limit
    Secondary earthingEarthed neutral, or left unearthed as an IT system
    Insulation monitoringRequired where the secondary is deliberately unearthed
    PhasesSingle-phase or three-phase, and whether a neutral is needed
    Enclosure and IP ratingOpen chassis for panel building, or a cabinet
    Site ambient temperatureState the design maximum inside the enclosure, not the room
    Load typeInstruments, drives, medical, tooling or test equipment
    QuantityUnits, and the circuits each must serve

    Standards we supply against

    • IEC 61558-1
    • IEC 61558-2-4