    Medium-voltage switchgear is bought as a fault-withstand assembly, and the figure that governs the whole enquiry is the short-circuit rating of the system it connects to. Every other decision follows from it: the busbar section, the circuit-breaker duty, the earthing arrangement and, most importantly, the internal arc classification. IEC 62271-200 lets a panel be classified for internal arc with the accessible sides identified, and that classification is what protects an operator standing in front of a panel when a fault develops inside it. A panel without it is not cheaper, it is a different product. Settle also whether the breakers are withdrawable — which is what allows maintenance without an outage on the whole board — and how cables enter, because top and bottom entry are not interchangeable once a switch room floor is poured. Send the single line diagram and the fault level study if you have them.

    What to state in your enquiry

    The more of this you send, the closer the first quotation lands.

    System voltageRated voltage and insulation level, at 60 Hz
    Short-circuit ratingRated short-time withstand current and its duration
    Busbar ratingContinuous current of the main and riser busbars
    Internal arc classificationIAC class and which sides are accessible to operators
    Breaker type and mountingVacuum or SF6, fixed or withdrawable
    Number of panelsIncomers, bus sections, feeders and any metering cubicle
    Protection and meteringRelay functions, CT and VT ratios, and comms protocol
    Cable entryTop or bottom, and the cable size and count per panel
    EarthingEarth switch, and the system earthing arrangement
    Enclosure and IP ratingIndoor switch room or outdoor kiosk
    Room environmentState the switch room ambient and whether it is cooled
    Utility approvalState if a utility or Aramco approved vendor list applies
    DocumentationSingle line diagram, type test reports and routine test certificates

    Standards we supply against

    • IEC 62271-1
    • IEC 62271-100
    • IEC 62271-200

    Which type do you need?

    Select one and it travels with your enquiry. Not sure? Leave it and describe the application instead.

    We source to specification. Send your requirement and we will come back with options, lead time and pricing.