A pressure relief valve is a safety device, and it is sized from the relieving scenario rather than from the line — fire case, blocked outlet, thermal expansion and control failure each give a different required orifice. Set pressure, back pressure and the relieving temperature all have to be stated, because built-up or superimposed back pressure changes whether a conventional valve is acceptable or a balanced bellows or pilot-operated design is required. These need a datasheet and usually certification.
The more of this you send, the closer the first quotation lands.
| Set pressure | State units and whether gauge or absolute |
|---|---|
| Relieving scenario | Fire case, blocked outlet, thermal expansion, control failure |
| Required relieving capacity | Mass or volume flow at relieving conditions |
| Back pressure | Superimposed and built-up; decides conventional vs bellows vs pilot |
| Valve type | Conventional, balanced bellows, or pilot operated |
| Orifice designation | API letter D through T, if already sized |
| Inlet and outlet size and rating | e.g. 2 in x 3 in, ASME 300 x 150 |
| Body and trim material | WCB, CF8M, Hastelloy; soft or metal seat |
| Fluid and phase | Gas, vapour, liquid, or two-phase |
| Relieving temperature | At the relieving condition, not normal operating |
| Certification | ASME Section VIII UV stamp, or PED, if required |
| Sour service | State if NACE MR0175 applies |
Select one and it travels with your enquiry. Not sure? Leave it and describe the application instead.
We source to specification. Send your requirement and we will come back with options, lead time and pricing.